Technical Data, Airius, UK

 

Electrical Data

Model No. Volts Hertz Watts RPM CFM Cubic m/hr
dB(A)
(At floor level)
 
10 - Short 230 50 12 980 318 540 25
15 230 50 15 1230 406 690 30
25 230 50 31 1450 460 780 34
45 
PS-4  230 50 42 1400 595 1010 34
PS-2  230 50 125 2450 1072 1821 49
60 230 50 120 1390 1667 2832 47
100 230 50 390 1690 3358 5705 43

 

Product Dimensions

Model No. Unit Weight (lbs/kg) Height to rim (Inches/mm) Height w/bail (Inches/mm) Diameter (Inches/mm)
 
10 - Short 7 / 3.2 12 / 305 16 / 410 13 / 330
15 9 / 4.1 16 / 410 22 / 560 13 / 330
25 9 / 4.1 16 / 410 22 / 560 13 / 330
45
PS-4 14 / 6.4 18 / 457 24 / 610 15 / 380
PS-2 14 / 6.4 18 / 457 24 / 610 15 / 380
60 22 / 10 24 / 610 32 / 813 18.25 / 464
100 42 / 20.5 33.25 / 845 N/A 19.5 / 495

 

Destratification fan Model number and Density guidelines

Ceiling Height

 

Model Number

Density of units (M² of floor space) v Level of activity
Meters Busy (office/retail) Medium (Factory) Clear (Warehouse/Hangar)
 2.5 10 60 70 80
3 10 55 65 75
3.5 10 50 60 70
4 15 80 90 95
4.5 15 70 80 85
5 15 60 70 75
 5.5 25 90 100 120
6 25 85 95 115
 6.5 25 80 90 110
7 25 75 85 105
7.5 25 70 80 100
8 25 65 75 95
8.5 45/PS-4 95 105 130
9 45/PS-4 90 100 125
9.5 45/PS-4 85 95 120
10 45/PS-4 80 90 115
10.5 45/PS-4 75 85 110
11 45/PS-4 70 80 105
11.5 45/PS-4 65 75 100
12 45/PS-4 60 70 95
13 45/PS-2 90 110 130
14 45/PS-2 80 100 120
15 60 155 175 210
16  60  150 170 200
17  60  145 165 190
18  60  140 160 180
19 100 170 210 250
20 100 170 210 250
21 100 170 210 250
22 100 170 210 250
23 100 170 210 250
24 100 170 210 250
25 100  170 210 250
26 100 170 210 245
27 100 170 210 240
28 100 170 210 235
29 100 170 200 230
30 100 165 195 225
31 100 160 190 220

 

1.     Free hanging units should be hung at between 300mm to 600mm below ceiling height
2.     The Airius units produce a column of air which should be directed to reach a floor surface
3.     To avoid annoyance be sure not to direct column over work stations
4.     The greater the amount of clutter (storage units, equipment, desks etc) the higher the density requirement
5.     This is for guidance purposes only, contact Airius Europe Ltd for actual specifications
 

PDF Download Technical Charts as PDF

 

PDF Datasheets

 

 

 

Noise Level − DBA Test – see Combined Model Data Sheet for DBA per model.

 
Noise is tested in accordance with ISO-3745 and ANSI 12.35 (not from 3 meters as quoted by some fan distributors).
 
Test conducted in an echo-free room with background noise lower than 15 DBA. The testing cooling fan runs in free airflow and a noise meter is set to 1 meter away from air entrance and at 90 Degrees to the fan. The test result is depicted with sound pressure level frequency band in DBAs.
 
The information below covers the full Airius range, both 120 vac and 230 vac where rated.
Result = 20 - 34 decibels at floor level, which is significantly less than any competing destratification fan at 3 meters − let alone at 1 meter!
 

PDF Click here to view noise level diagram

 

Warranty − Airius Destratification Ceiling Fans − All Models

 
Models 10, 15, 25, 45, 60 & 100 - Three Year Warranty
Free replacement – New. Customer or Distributor to return defective units to Airius Europe Ltd carriage paid. Upon receipt, Airius Europe Ltd will dispatch new units by return carriage paid.

 
Installation Service
Airius offer an installation service for orders of 8 units or more. We will be happy to quote you a competitive price.